Purpose

Battery unit VKT-7 is intended for metering and recording remote heat consumption monitoring and heating medium parameters in two closed and open water supply systems, each of which may include the following pipelines: supply, return, hot water supply, makeup or drinking water pipelines.

Application field

VKT-7 heat calculation unit is energy-independent, safe in operation and combines advantages of its best analogues. Due to "two units in single frame" concept, heat meters based on VKT-7 are the best solution for heat metering in housing and public utilities sector objects.
General technical specifications

There're 5 models of VKT-7 produced, with the following features:

Capabilities\Model 01 02 03 04 04P

Number of sensors connected

volume

4

4

6

6

6

 

temperature

2

2

5

5

5

 

pressure

4

5

Power control of network flow rate sensors

+

+

+

+

Additional discrete signals: one inout, two output*

+

+

+

+

Design service life of integrated battery, years

5

12

12

12

12

Extra battery*

RS485 interface: *

Note
* - shall be ordered additionally;

In 01 and 02 model ТВ2 contains only one pipeline. 03 and 04 models are measuring temperature: of the hot water supply system, TB1 system, air or cold water. 04P model allows using additional pressure sensor in 3 TB1 pipeline.

Functional capabilities

  • Application conditions setup from front panel;
  • Protection from unauthorized interference to device operation;
  • Selection of virtually any typical layout of three water meters in any ТВ1 and ТВ2 systems;
  • Selection of virtually any typical formula for calculation of total heat consumption in any ТВ1 and ТВ2 systems;
  • Viewing archives from VKT-7 front panel;
  • Setup of ending date of reporting month in monthly archive;
  • Metering algorithm control and selection in case water meters mains supply is turned off;
  • Metering algorithm control and selection in case setpoints of average hourly water consumption in system pipelines are reached;
  • Metering algorithm control and selection in case setpoints of water masses imbalance in system pipelines are reached;
  • Metering algorithm control and selection in case items of the formula for calculating total heat consumption of the system are negative;
  • Possibility to switch metering to summer heat consumption mode;
  • Possibility of measuring water pressure in system pipelines;
  • Possibility of measuring cold water temperatures;
  • Setup of time delay interval when printing report on printer;
  • Setup of time delay interval when copying archive to SP (Storage Panel);
  • Extra battery for powering ultrasonic flow meters;
  • Additional signals:
    • Count pulse input for connecting electricity meter or water meter;
    • Alarm input (security, fire alarm etc);
    • telemetric output - forming pulse signal when selected value of specified parameter is exceeded;
    • ALARM output - displaying situation for diagnosis at external indicator.

Recording measurement results indications

VKT-7 heat calculation unit archives 1,152 hourly, 128 daily and 32 monthly records and total indications of measurement results and diagnosis of heat supply parameters.
Current and archive indications are displayed at two-line indicator panel.

Metrologic characteristics

Relative error of indication, up to:

  • Heat energy ± (0.1 + 3/Δt)%;
  • Mass ± 0.1%;
  • Time ± 0.01%.

Absolute error in indication, up to:

  • Temperature difference ± 0.03°С;
  • Temperature ± 0.1°С;
  • Volume ± 1 unit ml of indication order.

Stated pressure indication error doesn't exceed ± 0.25%.
Calibration interval - 4 years.

Connection of sensors

Single-type resistance temperature device: 100P, Pt100, 100М, 500P and Pt500.
Volume transducers with pulse output passive - up to 16 Hz and potential - up to 1,000 Hz.  Pulse value 0.0001 – 10,000 liters.
Excess pressure transducers with signal 4-20 mА.

Interfaces

Information is sent to indicator and external devices (printer, PC, modem) via RS232 or RS485 interface.

Warranty period

Heat calculation unit warranty period - 6 years.